The important feature of hot water boiler is that fuel or natural gas, gas and other combustible gases are used as fuel for combustion. And with a high-tech full-active control system, it can fully supply hot water to meet people's needs.
Click apply
Fill out the form
Waiting for review
Contact you
Successful
Main description
The gas boiler is a horizontal quick-install internal combustion three-return fire tube boiler. The offset furnace is used in a wet-back structure, and the high-temperature flue gas flushes the second and third return pipes in turn, and then the rear smoke chamber is discharged into the atmosphere through the chimney. The boiler is equipped with a moving front and rear smoke box cover to make the boiler easy to repair. Boiler configuration technology superior performance burner, using active proportional adjustment of combustion, active regulation of water supply, program start and stop, full active operation and other advanced technology, and active protection of water temperature, flameout and other active protection. The boiler has the characteristics of compact structure, safety, easy operation, quick installation, less pollution, low noise and high compliance.
Performance advantage
1. Boiler design, production, supervision and inspection are strictly in accordance with "Steam Boiler Safety Supervision Regulations", JB/T 10094-2002 "General Technical Conditions for Industrial Boilers", JB/T 1609-2002 "Boiler Shell Boiler System" The technical conditions are implemented to ensure the long-term safety and stability of the boiler.
2. The main body is a three-way pyrotechnic tube structure with a full-wet back and back flow in the shell and shell, and the micro-positive pressure combustion in the large combustion chamber is effective, and the combustion heat load is low. Hazardous substances have low NOx emissions.
3. The corrugated furnace and the threaded pipe structure, not only improve the strength, but also meet the need for various parts of the thermal expansion.
4. The main welds are welded by butt joints, and the X-ray and ultrasonic waves are not damaged to ensure the welding quality meets the national requirements.
5. The boiler has large water capacity and strong adaptability to load. Well-designed in-pot assembly, steam water rate is less than 4%, meeting the high requirements of users for steam quality.
6. The use of new insulation materials, light weight, less heat loss, good insulation performance.
7. The water level alarm uses stainless steel as the electrode rod and PTFE as the insulation material. Inserted from above, not easy to smear, performance, long service life.
8. The front and rear smoke boxes are hinged for easy opening and easy maintenance.
9. Oxygen content adjustment (optional): The system can successfully detect the oxygen content in the flue gas, and transmit the data to the control system in real time. Through computer intelligent analysis, the ratio of the combustion equipment is actively adjusted to make it real-time. In a good working condition, the combustion obedience is greatly improved, which can greatly reduce the consumption of fuel.
10. Active control level.
11. The boiler controller adopts Siemens and Delixi electrical components, which not only has performance, but also realizes man-machine dialogue and long-distance control.
Model | RT series hot water boiler | ||||||||||||||
Rated thermal power (Mw) | 0.35 | 0.7 | 1.05 | 1.4 | 2.1 | 2.8 | 3.5 | 4.2 | 5.6 | 7 | 8.4 | 10.5 | 12.6 | 14 | |
Backwater temperature (°C) | 65 | ||||||||||||||
Outlet water temperature (°C) | 85 | ||||||||||||||
Boiler thermal efficiency (%) | 91—95 | ||||||||||||||
Fuel consumption | Diesel (Kg/h) | 32 | 65.4 | 98 | 131 | 196.2 | 261.6 | 327 | 392.4 | 523.2 | 654 | 784.8 | 981 | 1177 | 1310 |
Heavy oil (Kg/h) | 34 | 69.5 | 105 | 139 | 208.5 | 278 | 347.5 | 417 | 556 | 695 | 846 | 1042.5 | 1251 | 1390 | |
Natural gas (m3/h) | 39.5 | 79.3 | 119 | 159 | 237.9 | 317.2 | 396.5 | 475.8 | 644 | 793 | 951.6 | 1189.5 | 1427.4 | 1586 | |
Liquefied gas (m3/h) | 14.2 | 29 | 43.5 | 58 | 87 | 116 | 145 | 174 | 232 | 290 | 348 | 435 | 522 | 580 | |
City gas (m3/h) | 84 | 168.5 | 253 | 337 | 505.5 | 674 | 842.5 | 1011 | 1348 | 1685 | 2022 | 2527.5 | 3033 | 3370 | |
Boiler transportation dimension | Length (mm) | 2800 | 3500 | 4100 | 4500 | 4700 | 4550 | 5700 | 6300 | 7000 | 7200 | 7840 | 8100 | 8230 | 8250 |
Width (mm) | 1600 | 1600 | 1900 | 2000 | 2110 | 2210 | 2500 | 2600 | 2700 | 2800 | 2860 | 3100 | 3100 | 3400 | |
Height (mm) | 2000 | 2100 | 2310 | 2360 | 2470 | 2580 | 2800 | 2900 | 3200 | 3300 | 3300 | 3400 | 3400 | 3550 | |
Chimney diameter (mm) | 250 | 350 | 430 | 450 | 450 | 550 | 650 | 650 | 650 | 800 | 800 | 900 | 1200 | 1200 | |
Heating area (m2) | 3000 | 6000 | 9000 | 12000 | 18000 | 24000 | 30000 | 36000 | 48000 | 60000 | 72000 | 90000 | 108000 | 120000 | |
Hot Water supply capacity (t) | 7 | 15 | 22 | 30 | 45 | 60 | 75 | 90 | 120 | 150 | 180 | 225 | 270 | 300 |
1. Technical service: provide free consultation and suggestion, technical support and service by email/fax/telephone and lifetime technical support.
2. Customized service: product development and design according to different customer's different requirements.
3. After-sale service team: technical engineers available to service overseas if needed.
4. Installation: we can arrange engineers to install machines in customer's factory.
5. Maintenance: reply will be given within 48 hours once customer inform us any malfunction happened, we can also arrange engineers to customer's factory to main machines.
6. Training: normal machine is properly adjusted before delivery, you will be able to use the machines immediately and you will be able to get free training advice towards our machine in our factory.
7. Warranty: one year since the date of delivery.